Weight | 0.16 g |
---|---|
Dimensions | 112 × 17.5 × 110 mm |
Description |
10-CH digital output module / RS485 |
Power Supply |
10..40 Vdc; 19..28 Vac (50-60 Hz) |
Insulation |
1500 V ac |
Outputs |
10-CH optoisolated channels, mosfet semiconductor |
Output Protection |
From short circuit and overvoltage with 6..40 Vdc range |
Diagnostics |
Channel status, programmable |
Safe State |
Configurable at start up or in case of communication fault, programmable delay fron 50 to 250 ms |
Communication |
RS485 2 wire, ModBUS RTU slave protocol |
Mounting |
35 mm symmetrical DIN (46277) rail |
Z-10-D-OUT
10-CH digital output module / RS485
The Z-10-D-OUT is used to drive N.10 MOSFETS from all of the control systems which are able to communicate with the transmission protocol MODBUS RTU through the RS485 serial interface. The digital output max load is 0,5 A (inductive) and 0,5 A (resistive) with maximum switch-on / switch-off cycle frequency of 2 cycles/second. The module is ModBUS Slave and can be coupled with any ModBUS Master device. A 3-way galvanic isolation among Power supply // output // RS485 circuits assures the integrity of your data.
Additional information
Related products
ZC-24DI
24 CH digital input CANopen / ModBUS RS485
ZC-24DI is used to interface N.24 digital signals (PUSH BUTTON, LIMIT SWITCH, REMOTE, CONTROL SWITCH, RELAIS etc.) with all of control systems which are able to communicate by the protocols CANopen or ModBUS RTU (protocol selectable through dip-switch). It disposes of 32 bit counters (N.8), maximum frequency input is 10 KHz. A 3-way galvanic isolation among Power supply // input // RS485 circuits assures the integrity of your data.
Z-D-IN
5-CH Digital input module / RS485
The Z-D-IN is used to interface 5 digital signals (PUSH BUTTON, LIMIT SWITCH, REMOTE, CONTROL SWITCH, RELAIS etc.) with all of control systems which are able to communicate by the protocol MODBUS RTU through the RS485 serial interface. A 16 bit counter is available on each input, the maximum frequency input is 100 Hz and it is possible to set one input as a fast counter with a maximum frequency of 10kHz. The module is ModBUS Slave and can be coupled with any ModBUS Master device.
ZC-16DI-8DO
16 CH digital input - 8 CH digital output CANopen / ModBUS RS485
The ZC-16DI-8DO is an 16 CH input / 8 CH output mixed module. The inputs have 32-bit counters / 10 kHz max frequency, mosfet Outputs with shared negative pole. The communication protocols are CANopen or ModBUS RTU (protocol selectable through dip-switch). A 3-way galvanic isolation among Power supply // input // RS485 circuits assures the integrity of your datas.
ZC-24DO
4 CH digital output CANopen / ModBUS RS485
ZC-24DO is used to drive N.24 MOSFETS from all of the control systems which are able to communicate by the protocols CANopen or ModBUS RTU (protocol selectable through dip-switch). The digital output max load is 0,5 Awith ON/OFF delay of 1ms. A 3-way galvanic isolation among Power supply // output // RS485 circuits assures the integrity of your data.
Z-5DI-2DO
Multifunction digital module with 5 inputs, 2 outputs and RS485 interface
Z-5DI-2DO is a mixed digital module with Micro USB front port of programming, 5 digital inputs (Redd, Proximity, PNP, NPN, contact) selectable via software, nr.5 totalizers @ 32bit with maximum frequency 5 kHz and settable forwards or backwards, nr.2 SPST relay outputs 2 A 250 Vac NO / NC type selectable via jumper. All totalizers are stored in non-volatile memory (FeRAM). For each input the module offers the measure of period, frequency, TON, TOFF.
Z-D-OUT
5-CH Digital output module / RS485 with a micro USB port on the front panel
The Z-D-OUT (hw.1with micro USB port on the front panel) is used to drive N.5 SPST relays from all of the control systems which are able to communicate with the transmission protocol MODBUS RTU through the RS485 serial interface. The instrument has N.5 SPST relays, capacity resistive loading of 5 A 250Vac, inductive loading of 2 A. The module is ModBUS Slave and can be coupled with any ModBUS Master device. 3-way galvanic isolation among Power supply // output // RS485 circuits assures the integrity of your data.